Skip to main content
Transition from Spectra™ to Tmax® XT
Information to assist with your migration
Banner default
Product Comparison
Select a Spectra Frame to view Tmax XT comparison
  Spectra SE Tmax XT1 Tmax XT2
Frame size (A) 150 125 125
Poles 2, 3 3, 4 3, 4
Interrupt rating (kA) 240 V AC 18, 65, 100, 200 50, 65, 100 65, 100, 150, 200
480 V AC 18, 25, 65, 100 25, 35, 65 25, 35, 65, 100, 150, 200
600 V AC 14, 18, 25 18, 22, 25, 35, 42
Dimensions (in.) Width 4.12 3.00 3.54
Depth 3.38 2.75 3.25
Height 6.31 5.12 5.12
Trip Units TMF X X
TMA X
Ekip DIP X
Ekip Touch X
RMS X
microEntelliGuard
  Spectra SF Tmax XT3 Tmax XT4
Frame size (A) 250 225 250
Poles 2, 3 3, 4 3, 4
Interrupt rating (kA) 240 V AC 65, 100, 200 50, 65 65, 100, 150, 200
480 V AC 35, 65, 100 25, 35 25, 35, 65, 100, 150, 200
600 V AC 22, 25 18, 22, 25, 50, 65, 100
Dimensions (in.) Width 4.12 4.13 4.13
Depth 3.81 2.75 3.25
Height 10.12 5.90 6.30
Trip Units TMF X X
TMA X
Ekip DIP X
Ekip Touch X
RMS X
microEntelliGuard
  Spectra SG Tmax XT5
Frame size (A) 600 600
Poles 2, 3 3, 4
Interrupt rating (kA) 240 V AC 65, 100, 200 65, 100, 150, 200
480 V AC 35, 65, 100 35, 50, 65, 100, 150, 200
600 V AC 25, 65 18, 25, 35, 65, 100
Dimensions (in.) Width 5.50 5.51
Depth 3.81 4.07
Height 10.09 8.07
Trip Units TMF
TMA X
Ekip DIP X
Ekip Touch X
RMS X
microEntelliGuard X
  Spectra SK Tmax XT6 Tmax XT7
Frame size (A) 1200 800 1200
Poles 2, 3 3, 4 3, 4
Interrupt rating (kA) 240 V AC 65, 100, 200 65, 100, 200 65, 100, 200
480 V AC 50, 65, 100 35, 50, 65 50, 65, 100
600 V AC 22, 42, 65 20, 25, 35 25, 50, 65
Dimensions (in.) Width 8.25 8.27 8.27
Depth 5.50 4.07 6.57
Height 15.50 10.55 10.55
Trip Units TMF
TMA X
Ekip DIP X X
Ekip Touch X
RMS X
microEntelliGuard X

 

 

Tmax XT and Spectra trip unit capability

Features TMF TMA Ekip DIP Ekip Touch RMS microEntelliguard
Standard protection X X X X X X
LSIG X X X
Adjustability to 40% of rating X X X X
Connectivity and communication X X
Embedded advanced functions X X
Online upgradability X X

Related Links

  • Spectra to SACE Tmax XT Distributor Migration Guide PDF

    This document will guide you through the Tmax XT frames and common accessories and explain how they compare to Spectra; highlight the frames and other details for common applications; and provide guidance on initial stocking options.

  • Conversion Guide: Spectra to Tmax XT molded case circuit breakers PDF

    The full guide for migrating from the Spectra range to the Tmax XT range. Includes product number specifications, product number structuring, cross-reference data and questions to ask your customer when migratiing.

  • Quick Reference Guide PDF

    A one-page PDF showing the quick reference tables displayed above and comparing the specifications for the Spectra range and the Tmax XT range.

  • Spectra to Tmax XT Smart Cross Reference Tool XLS File

    A downloadable smart cross reference tool.

  • Tmax XT Range

    Complete information on the Tmax XT molded case circuit breaker product offer.